HVAC Information

Heat Load Calculation

Formula: Q = Area (sq.ft) x Heat Load Factor (BTU/hr per sq.ft)

Example: 500 sq.ft office: Q = 500 x 30 = 15,000 BTU/hr TR = 1.25

CFM Calculation

Formula: CFM = Sensible Heat (BTU/hr) / (1.08 x Delta T)

Example: 12,000 BTU/hr, Delta T = 20°F CFM = 556 →

AHU / FCU Sizing

Rule: 1 TR = 400 CFM

Duct Sizing Heat Load Calculat

Velocity Limits:

Main: 1400-1800 FPM

800 CFM @ 1000 FPM 0.8 sq.ft 14"x10"

Chilled Water Flow Rate

Formula: GPM = BTU/hr/ (500 x Delta T)

Example: 24,000 BTU/hr GPM = 4.8

Pipe Sizing

Chiller Sizing

Formula: TR = BTU/hr / 12,000

Example: 60,000 BTU/hr 5 TR

Cooling Tower Sizing

Rule:

Heat Rejection = 1.25 x Load

10 TR → Tower = 12.5 TR
.
.
#Hvac #hvacformula #fblifestyle #HVACMaintenance #hvactechnician
HVAC Duct Installation Techniques
Complete diagram of the refrigeration cycle with additional equipment (oil separator, filter, mirror etc.) ) commonly used in large-scale refrigeration systems.
Hello Dear friends HVAC Technician team important question ❓🤔 #activefollowers #Refrigerator #AC #trending #hvactechnician #hvac
#fblifestyle
"Explore the different types of pumps used in various industries! From positive displacement pumps like rotary and reciprocating pumps to non-positive displacement pumps like centrifugal and axial flow pumps – each plays a critical role in fluid movement and processing. Ideal for engineering, industrial, and mechanical applications. ⚙️💧"

#TypesOfPump #PositiveDisplacement #NonPositiveDisplacement #RotaryPump #ReciprocatingPump #CentrifugalPump #AxialFlowPump #PistonPump #GearPump #ScrewPump #PumpTechnology #FluidHandling #IndustrialPumps #MechanicalEngineering #EngineeringSolutions #ProcessIndustry
#fblifestyle
use of new technology
What is the difference between Pressure 𝐑𝐞𝐥𝐢𝐞𝐟 𝐕𝐚𝐥𝐯𝐞and Pressure 𝐒𝐚𝐟𝐞𝐭𝐲 𝐕𝐚𝐥𝐯𝐞

You see these devices on tanks, pipelines, and boilers. Many engineers just call them “safety valves.” But there’s a big difference, and knowing it can prevent equipment damage or worse, a plant incident.

𝐏𝐫𝐞𝐬𝐬𝐮𝐫𝐞 𝐑𝐞𝐥𝐢𝐞𝐟 𝐕𝐚𝐥𝐯𝐞 (𝐏𝐑𝐕):

Protects 𝐥𝐢𝐪𝐮𝐢𝐝 𝐬𝐲𝐬𝐭𝐞𝐦𝐬 from overpressure during normal operation.

Opens 𝐠𝐫𝐚𝐝𝐮𝐚𝐥𝐥𝐲 as pressure rises above the set point.

Common on pump discharge lines, tanks, and heat exchangers.

𝐏𝐫𝐞𝐬𝐬𝐮𝐫𝐞 𝐒𝐚𝐟𝐞𝐭𝐲 𝐕𝐚𝐥𝐯𝐞 (𝐏𝐒𝐕):

Protects 𝐠𝐚𝐬 𝐨𝐫 𝐬𝐭𝐞𝐚𝐦 𝐬𝐲𝐬𝐭𝐞𝐦𝐬 from sudden extreme overpressure.

Opens fully and instantly at the set pressure.

Common on boilers, gas pipelines, and pressure vessels.

𝐊𝐞𝐲 𝐝𝐢𝐟𝐟𝐞𝐫𝐞𝐧𝐜𝐞:

PRV = controlled relief, usually for liquids.

PSV = emergency relief, usually for gases or steam.