Cooling Tower Complete Calculations Package With Examples
Cooling Tower Design 101 All Calculations in One Place
Perfect for engineers working in pharma, chemical, HVAC, or utilities - here's your complete cheat sheet
1. Range
Formula: Range = Hot water temp - Cold water temp
Example: 42°C 32°C = 10°C
2. Approach
Formula: Approach = Cold water temp - Wet bulb temp
Example: 32°C - 29°C = 3°C
3. Cycle of Concentration (COC)
Formula: COC = TDS in circulating water / TDS in
makeup water
Example: 1800 ppm / 600 ppm = 3
4. Evaporation Loss
Formula: Evap = 0.00085 × Circulation Rate × Range
For 500 m³/hr and 10°C
Evap = 0.00085 x 500 x 10 = 4.25 m³/hr
5. Blowdown Loss
Formula: Blowdown = Evaporation / (COC - 1)
4.25/(3-1) = 2.125 m³/hr
9. Sump Volume (Water Level)
Formula: Sump = Retention Time (min) x Flow Rate ÷
60
5x50060 = 41.67 m³
10. Cooling Tower Capacity
Formula: Flow (m³/hr) = TR x 0.154
For 760 TR 760 x 0.154 = 117.04 m³/hr
Quick Summary Table
Parameter Formula / Value Example Value
Range: Hot temp - Cold temp 10°C
Approach: Cold - Wet bulb temp 3°C
COC: TDS ratio 3
Evaporation: 0.00085 × Flow × Range 4.25 m³/hr
Blowdown: Evap / (COC-1) 2.125 m³/hr
Drift Loss: 0.001 x Flow0.5 m³/hr
Side Stream Filter: 5% of Flow 25 m³/hr
Backwash: 3% of Side Stream0.75 m³/day
Sump Volume: (5 min x Flow) / 60 41.67 m³
Cooling Capacity: TR × 0.154 117.04 m³/hr.
Engineers, let's move beyond theory and apply these in real-world systems.
Drop a if you've used these in your plant!
Feel free to save, share, or bookmark this post
#CoolingTower #ProcessEngineering #WaterBalance
#UtilitiesDesign #PharmaEngineering #PlantDesign
#PumpSizing #ChemicalEngineering #HVACDesign
#TRtoFlow
Cooling Tower Design 101 All Calculations in One Place
Perfect for engineers working in pharma, chemical, HVAC, or utilities - here's your complete cheat sheet
1. Range
Formula: Range = Hot water temp - Cold water temp
Example: 42°C 32°C = 10°C
2. Approach
Formula: Approach = Cold water temp - Wet bulb temp
Example: 32°C - 29°C = 3°C
3. Cycle of Concentration (COC)
Formula: COC = TDS in circulating water / TDS in
makeup water
Example: 1800 ppm / 600 ppm = 3
4. Evaporation Loss
Formula: Evap = 0.00085 × Circulation Rate × Range
For 500 m³/hr and 10°C
Evap = 0.00085 x 500 x 10 = 4.25 m³/hr
5. Blowdown Loss
Formula: Blowdown = Evaporation / (COC - 1)
4.25/(3-1) = 2.125 m³/hr
9. Sump Volume (Water Level)
Formula: Sump = Retention Time (min) x Flow Rate ÷
60
5x50060 = 41.67 m³
10. Cooling Tower Capacity
Formula: Flow (m³/hr) = TR x 0.154
For 760 TR 760 x 0.154 = 117.04 m³/hr
Quick Summary Table
Parameter Formula / Value Example Value
Range: Hot temp - Cold temp 10°C
Approach: Cold - Wet bulb temp 3°C
COC: TDS ratio 3
Evaporation: 0.00085 × Flow × Range 4.25 m³/hr
Blowdown: Evap / (COC-1) 2.125 m³/hr
Drift Loss: 0.001 x Flow0.5 m³/hr
Side Stream Filter: 5% of Flow 25 m³/hr
Backwash: 3% of Side Stream0.75 m³/day
Sump Volume: (5 min x Flow) / 60 41.67 m³
Cooling Capacity: TR × 0.154 117.04 m³/hr.
Engineers, let's move beyond theory and apply these in real-world systems.
Drop a if you've used these in your plant!
Feel free to save, share, or bookmark this post
#CoolingTower #ProcessEngineering #WaterBalance
#UtilitiesDesign #PharmaEngineering #PlantDesign
#PumpSizing #ChemicalEngineering #HVACDesign
#TRtoFlow